Modular device for DIN-EN 60715 TH35 rail mounting. 1 module = 18mm wide, 58mm deep.
State-of-the-art hybrid technology combines advantages of nonwearing electronic control with
high capacity of special relays.
Connection to the Eltako RS485 bus, terminals RSA and RSB.
Up to a total of 128 actuators can be added in this way.
Patented Eltako Duplex technology (DX) allows you to switch normally potential free contacts
in zero passage switching when 230V A/C voltage 50Hz is switched. This drastically
reduces wear. To achieve this, simply connect the N conductor to the terminal (N) and L to
K(L). This results in an additional standby consumption of only 0.1 watt.
The 12V DC supply voltage of the complete RS485 bus is mainly powered at 6W, 12W or
24W by a switch mode power supply unit SNT12-12V DC that is only 1 or 2 pitch units wide.
When all 3 relays of the F4L12 are switched on, 0.7 watt are required.
The top rotary switch
is required for teach-in.
Middle rotary switch
for operating modes:
AUTO1:
The 4 contact surfaces are assigned 'exclusively' when a wireless pushbutton with
double rocker is taught-in as follows: top left closes Contact 1; bottom left closes Contact
2; top right closes Contact 3; bottom right closes Contact 4 (switch-off function). All other
contacts are opened. Wireless window/door contact FTK or Hoppe window handles closes
Contact 4 'exclusively' when a window is opened. A wireless transmitter module can also be
taught-in to close Contact 4 'exclusively'.
AUTO2:
Same as AUTO1, but a wireless pushbutton with double rocker is assigned 'adding':
top left closes Contact 1; bottom left closes Contacts 1 and 2; top right closes Contacts 1, 2
and 3; bottom right closes Contact 4 (switch-off function). All other contacts are opened.
AUTO3:
Activating with wireless CO2 sensor. The contacts close 'exclusively'.
AUTO4:
Same as AUTO3, but activated by the wireless humidity sensor.
AUTO5:
Same as AUTO3, but activated by the wireless temperature sensor.
AUTO6:
Same as AUTO3, but the contacts close 'adding'.
AUTO7:
Same as AUTO4, but the contacts close 'adding'.
AUTO8:
Same as AUTO5, but the contacts close 'adding'.
The bottom and top rotary switches
are used when sensor activation AUTO3 to AUTO8 are in
operation
to set the switch-on threshold for Contact 1 and to set the additional value at which
Contacts 2 and/or 3 close.
Overview of switch-on thresholds
(lower rotary switch):
CO
2 (ppm):
1 = 700ppm; 2 = 800ppm; 3 = 900ppm; 4 = 1000ppm; 5 = 1200ppm;
6 = 1400ppm; 7 = 1600ppm; 8 = 1800ppm, 9 = 2000ppm and 10 = 2200ppm.
Humidity (%):
1 = 10%, 2 = 20%, ... 10 = 100%.
Temperature (°C):
1 = 20°C, 2 = 22°C, 3 = 24°C, ... 10 = 38°C.
Overview of addition values
(upper rotary switch):
CO
2 difference:
1 = 50ppm, 2 = 100ppm, 3 = 150ppm, ... 10 = 500ppm.
Fixed hysteresis: 50ppm.
Humidity difference:
1 = 5%, 2 = 10%, 3 = 15%, ... 10 = 50%. Fixed hysteresis: 5%.
Temperature difference (K):
1 = 1K, 2 = 2K, 3 = 3K, ... 10 = 10K.
Fixed hysteresis: 1K.
The LED
below the upper function rotary switch performs during the teach-in process according
to the operation manual. It shows control commands by short flickering during operation.