Modular device for DIN-EN 60715 TH35 rail mounting. 1 module = 18mm wide, 58mm deep.
Connection to the Eltako RS485 bus, terminals RSA and RSB.
Up to a total of 128 actuators can be added in this way.
Up to 35 pushbuttons each with 4 functions can be assigned to each channel, of which one
or more central pushbuttons.
Switching voltage 230V.
Zero passage switching to protect contacts and consumers.
The 12V DC supply voltage of the complete RS485 bus is mainly powered at 6W, 12W or
24W by a switch mode power supply unit SNT12-12V DC that is only 1 or 2 pitch units wide.
When the relay of the FTN12 is switched on, 0.3 watt are required.
After installation, wait for short automatic synchronisation before the switched consumer is
connected to the mains.
If the function TLZ is set, the lighting is switched on again after a power failure provided the set
time has not yet elapsed.
In addition to the bus control input, this staircase off-delay timer can also be controlled locally
by a conventional 230V control switch. Glow lamp current up to 5mA, dependent on the
ignition voltage of the glow lamps.
The upper rotary switch LRN
is required for teach-in. Then the off-delay 1 to 30 minutes can
be set.
Use the middle rotary switch
in position LRN to assign up to 35 switches and/or wireless
motion/brightness sensors FBH via a wireless antenna module FAM12-12V DC, of which one
or several may be central control switches. The required function of this staircase off-delay
timer can then be selected:
NLZ
= off-delay timer with adjustable operate delay
TLZ
= staircase time switch
ESL
= staircase time switch for energy saving lamps ESL
+ = with pushbutton permanent light (only TLZ)
+ = with switch-off early warning (TLZ + ESL)
+ = with pushbutton permanent light and switch-off early warning (TLZ + ESL)
If the permanent light function
is switched on, the function can be activated by pressing
the pushbutton for longer than 1 second. This function switches off automatically after
60 minutes or by pressing the pushbutton for longer than 2 seconds.
If the switch-off early warning
is switched on, the light starts to flicker approx.
30 seconds before time-out. This is repeated three times at decreasing time intervals.
If both switch-off early warning and pushbutton permanent light are switched on,
switch-off early warning is activated before automatic switch-off of the permanent light.
With the bottom rotary switch
an operate delay (AV-time) can be set at NLZ.
Setting AUTO 1 = 1s, AUTO 2 = 30s, AUTO 3 = 60s, AUTO 4 = 90s und AUTO 5 = 120s (right
stop). Also permanent light function can be set manually.
When teaching-in
wireless motion/brightness sensors FBH, the switching threshold is
defi ned on the last FBH taught-in to switch the light on/off depending on the brightness
provided motion is detected. The off delay set on the FTN12 is prolonged by a setting of
1 minute fixed in the FBH.
When teaching-in
wireless window/door contacts FTK, a NC or NO can be taught-in as required.
Accordingly, the timing period starts when opening or closing the window or the door.
If
switches for permanent operation are taught-in, for example wireless transmitter modules
or FTS12EM, it is switched on when pressing and the time will be started when releasing.
The LED
below the upper function rotary switch performs during the teach-in process according
to the operation manual. It shows control commands by short flickering during operation.